Pagá en cuotas

Llega gratis entre el jueves y el martes 11/jun

Retirá gratis entre el jueves y el martes 11/jun en correo y otros puntos

Ver en el mapa

Stock disponible

ELECTRICA BOULEVARD

MercadoLíder Platinum

+1000

Ventas concretadas

Brinda buena atención

Medios de pago

Hasta 12 cuotas sin tarjeta

Mercado Crédito

Tarjetas de crédito

Visa
American Express
Mastercard
Naranja

Tarjetas de débito

Visa Débito
Maestro
Cabal Débito
Mastercard Débito

Efectivo

PagoFacil
Rapipago

Descripción

General Information
Extended Product Type:TA25DU-5.0M
Product ID:1SAZ211201R2035
EAN:4013614482519
Catalog Description:TA25DU-5.0M Thermal Overload Relays
Long Description:TA25DU-5.0M (3.5-5.0A) thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10A. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
Categories
Products » Low Voltage Products and Systems » Control Products » Contactors » Thermal Overload Relays

TA25DU-5.0M - image 0
Ordering
Minimum Order Quantity:1 piece
Customs Tariff Number:85364900
Popular Downloads
Instructions and Manuals:2CDC106031M6802
Time-Current Characteristic Curve:1SAZ200501F0011
CAD Dimensional Drawing:2CDC001079B0201
Dimensions
Product Net Width:44 mm
Product Net Height:80 mm
Product Net Depth / Length:94 mm
Product Net Weight:0.15 kg
Technical
Rated Operational Voltage:Main Circuit 690 V AC
Main Circuit 440 V DC
Rated Operational Current (Ie):5 A
Rated Frequency (f):Auxiliary Circuit 50 Hz
Auxiliary Circuit 60 Hz
Auxiliary Circuit DC
Main Circuit 60 Hz
Main Circuit 50 Hz
Main Circuit DC
Number of Poles:3
Number of Auxiliary Contacts NC:1
Number of Auxiliary Contacts NO:1
Number of Protected Poles:1
Conventional Free-air Thermal Current (Ith):Auxiliary Circuit NC 5 A
Auxiliary Circuit NO 5 A
Degree of Protection:Housing IP20
Main Circuit Terminals IP10
Pollution Degree:3
Connecting Capacity Auxiliary Circuit:Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 0.75 ... 4 mm²
Connecting Capacity Main Circuit:Flexible with Ferrule 1x 0.75 ... 4 mm²
Flexible with Ferrule 2x 0.75 ... 4 mm²
Flexible 1x 0.75 ... 4 mm²
Flexible 2x 0.75 ... 4 mm²
Rigid 1x 0.75 ... 4 mm²
Rigid 2x 0.75 ... 4 mm²
Recommended Screw Driver:Auxiliary Circuit Pozidriv 1
Main Circuit Pozidriv 2
Power Loss:at Rated Operating Conditions per Pole 1.1 ... 2.2 W
Suitable For:AX09
AX12
AX18
AX25
AX32
AX40
Standards:CSA 22.2 No. 14
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 508
Technical UL/CSA
Maximum Operating Voltage UL/CSA:Main Circuit 600 V AC
Contact Rating UL/CSA:(NC:) B600
(NO:) C600
Connecting Capacity Main Circuit UL/CSA:Flexible 1/2x 16-8 AWG
Stranded 1/2x 16-8 AWG
Connecting Capacity Auxiliary Circuit UL/CSA:Flexible 1/2x 18-14 AWG
Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSA:Auxiliary Circuit 12 in·lb
Main Circuit 12 in·lb
Environmental
Ambient Air Temperature:Operation -25 ... +55 °C
Operation Compensated -25 ... +55 °C
Storage -40 ... +70 °C
Maximum Operating Altitude Permissible:2000 m
Resistance to Shock acc. to IEC 60068-2-27:25g / 2 shocks / 13 ms
RoHS Status:Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Preguntas y respuestas

¿Qué querés saber?

Nadie hizo preguntas todavía. ¡Hacé la primera!